The height, length and resulting air velocities greatly figure in
everything in determining the size and performance of a coil. Step # 1
in determining the size and performance of a coil is dependent upon
understanding face & air velocities of air across the coil. Whether you
use a coil selection program to help size the coil, or you are replacing
an existing coil; the height, length and resulting velocity determine
everything.
Hot Water Booster Coils
Every
coil has a specific, optimum velocity, so you want to make sure you are
within 30% (+ or -) of that number. For example, booster coils have an
optimum velocity of 800 ft/minute. That means that you can drop your
velocity to 600 ft/minute, or conversely, increase the velocity to 1,000
ft/minute. The duct velocities are almost always higher, which means
that you will need to transition to a larger coil. Try to get to as
close to 800 ft/minute as possible, while sizing your coil to make the
transition as easy as possible. Everything with coils is a balancing
act.
Hot Water & Steam Coils
Like booster coils, hot water and steam coils should also have face
velocities at approximately 800 ft/minute. Both steam & hot water
coils have only sensible heating, which is why their face velocities can
be the same. Face velocities ultimately control the coil’s cost, so 800
ft/minute really is a heating coil’s “sweet spot”.
If you are purchasing an air handler unit, oftentimes the heating coil
is smaller than the cooling coil because the face velocities on heating
coils can exceed those of cooling coils. Due to water carry-over,
cooling coils cannot exceed 550 ft/minute, while heating coils only deal
with sensible heat.
Chilled Water & DX Coils
Due to the limited face velocities of cooling coils, your choices are
more limited. With cooling coils, your face velocity must be somewhere
between 500 ft/minute-550 ft/minute. Remember that when dealing with
cooling coils, you are dealing with both sensible and latent cooling, so
the coil is wet. When you exceed 550 ft/minute, water carry-over occurs
past the drain pans.
If you are purchasing an air handler unit, you probably will not have
worry about the coil’s face velocity as most coils come pre-sized at
acceptable face velocities. Fan coils also come pre-sized with the
correct CFM’s. However, if you are replacing an existing cooling
coil, the face velocity must remain at or below 550 ft/minute!!
Air
Stratification Across the Coil
Air does not travel equally across the face of a coil. If you were to
divide a coil into 9 equal sections, like a tic-tac-toe board, you would
see a high percentage of air travelling through the center square,
rather than the corner squares. In a perfect air flow scheme, 11% of the
air would travel through each of the 9 squares, but that is not what
happens. Because more air travels through the center of the coil, you
want to avoid putting a fan too near the coil. Due to central air
flows, most systems are draw-thru, rather than blow-thru. This is also
why you want to avoid installing your coil near any 90-degree
angles/turns in the ductwork. Avoid any situations that contribute more
than the “natural” air stratification to help ensure your coil is at
maximum efficiency.
In some situations, involving cooling coils, you will have water
carry-over even when the coil is sized correctly. How can this happen?
Think about the tic-tac-toe board again. Air velocities are exceeding
700 ft/minute in the coil’s center, while the corners are around 300
ft/minute. This cannot and will not work.
Coils do not have any moving parts. They simply react to the air across
the outside of the coil and whatever is running through the inside of
the coil. Coils are 100% a function of your entire system, as well as
the installation in general.
|